en:hems_v1_2_0:methods_resources:firmwareupdate
Differences
This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
en:hems_v1_2_0:methods_resources:firmwareupdate [2021/10/28 07:57] – neoxy | en:hems_v1_2_0:methods_resources:firmwareupdate [2021/10/28 13:22] (current) – neoxy | ||
---|---|---|---|
Line 4: | Line 4: | ||
===== CyBroBinLoader software ===== | ===== CyBroBinLoader software ===== | ||
- | * Download latest CyBroBinLoader.exe from www.cybrotech.com | + | * Download latest CyBroBinLoader.exe from https://www.cybrotech.com/ |
* Run CybroBinLoader.exe | * Run CybroBinLoader.exe | ||
- | * In case Windows OS is blocking execution, click on more info and run anyway | + | * In case Windows OS is blocking execution, click on "more info" |
{{ hiq_energy: | {{ hiq_energy: | ||
Line 16: | Line 16: | ||
===== Firmware upload ===== | ===== Firmware upload ===== | ||
- | * Download latest HEMS firmware from: en: | + | * Download latest HEMS firmware from [[en:hems_v1_2_0: |
+ | * Select correct Cybro NAD (sticker on top or side of MC controller) | ||
+ | * Select firmware under PLC program | ||
+ | * Enable PLC program and Start PLC | ||
+ | * Click send | ||
+ | * :!: PC must be on the same network as MC controller | ||
+ | * :!: Do not interrupt durring update process | ||
+ | * :!: HEMS configuration may be lost, use BACKUP before update and later RESTORE as described under [[en: | ||
+ | |||
+ | {{ hiq_energy: | ||
+ | |||
+ | {{ hiq_energy: | ||
<WRAP clear></ | <WRAP clear></ | ||
- | |||
- | ===== Installation and mounting ===== | ||
- | * :!: Carefully open WM-1 module and configure serial communication with jumpers. (Default configuration is 9600bps, 8N1 with normal timeout) | ||
- | * :!: Place WM-1 module at least 10cm from other objects. Installation is not recommended inside metal cabinets. | ||
- | * Connect RS485 terminals to WM-1 RS485 terminals | ||
- | * A - A | ||
- | * B - B | ||
- | * C - GND | ||
- | * Connect to 230V power supply | ||
- | * Configure radio pairing | ||
- | |||