Line 4: Line 4:
  
 ===== Page 1- Power distribution-RCD switch and power meter ===== ===== Page 1- Power distribution-RCD switch and power meter =====
-Single phase power input, connection of RCD switch (Residual Current Device) and [[en:hiq_home:hardware:pm-1-iq|power meter]].\\+Single phase power input, connection of RCD switch (Residual Current Device) and [[en:hiq_hw:pm-1-iq|power meter]].\\
 Input can be single or three phase. \\ Input can be single or three phase. \\
-The [[en:hiq_home:hardware:pm-1-iq| power meter]] on the wiring plan is connected to measure the whole electricity consumption, but can be connected to any device (or group of devices). Only single phase electricity measurement is available.\\+The [[en:hiq_hw:pm-1-iq| power meter]] on the wiring plan is connected to measure the whole electricity consumption, but can be connected to any device (or group of devices). Only single phase electricity measurement is available.\\
 \\ \\
 {{hiq_building_automation:hiq_home:methods:designing:designing01.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing01.png?nolink&800}}\\
Line 17: Line 17:
  
 ===== Page 4 - Control System-Power supply, HC, CAD-232  ===== ===== Page 4 - Control System-Power supply, HC, CAD-232  =====
-[[en:hiq_home:hardware:ps-iq|24V power supply (PS) ]] for control system, [[en:hiq_home:hardware:hc-iq| Home controller]]  and [[en:hiq_home:hardware:pm-1-iq| CAD-232-A2-IQ]]. \\ +[[en:hiq_hw:ps-iq|24V power supply (PS) ]] for control system, [[en:hiq_hw:hc-iq| Home controller]]  and [[en:hiq_hw:pm-1-iq| CAD-232-A2-IQ]]. \\ 
-[[en:hiq_home:hardware:ps-iq|24V power supply ]]  can be optionally used for LED lighting (up to 2.5A with serial power supply, larger power supply can be used). \\ +[[en:hiq_hw:ps-iq|24V power supply ]]  can be optionally used for LED lighting (up to 2.5A with serial power supply, larger power supply can be used). \\ 
- [[en:hiq_home:hardware:hc-iq| Home controller (HC) ]] is the heart of the system. It is connected to the network (ETH) and has optional inputs (connections are on page [[en:hiq_home:methods:design#page_15_home_controller_inputs|15]]) and outputs (connections are on page [[en:hiq_home:methods:design#page_16_home_controller_outputs|16]]).\\ + [[en:hiq_hw:hc-iq| Home controller (HC) ]] is the heart of the system. It is connected to the network (ETH) and has optional inputs (connections are on page [[en:hiq_home:methods:design#page_15_home_controller_inputs|15]]) and outputs (connections are on page [[en:hiq_home:methods:design#page_16_home_controller_outputs|16]]).\\ 
-[[en:hiq_home:hardware:pm-1-iq|CAD-232-A2-IQ]] expander is used as communication interface between home controller and power meter (If power meter is not used then the expander is not necessary).  It is connected to a home controller through IEX bus, to COM2 on home controller input and to power meter (RS485 communication).\\+[[en:hiq_hw:pm-1-iq|CAD-232-A2-IQ]] expander is used as communication interface between home controller and power meter (If power meter is not used then the expander is not necessary).  It is connected to a home controller through IEX bus, to COM2 on home controller input and to power meter (RS485 communication).\\
 \\ \\
 {{hiq_building_automation:hiq_home:methods:designing:designing04.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing04.png?nolink&800}}\\
Line 30: Line 30:
 {{hiq_building_automation:hiq_home:methods:designing:designing06.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing06.png?nolink&800}}\\
 ===== Page 7 – CS - Light dimmer  ===== ===== Page 7 – CS - Light dimmer  =====
-Up to 4 light dimmers can be connected to 1 HC. On sample plan we use 2 [[en:hiq_home:hardware:ld-p4-iq|Light dimmers drivers]] for [[en:hiq_home:hardware:lud12-iq|LUD-12]] universal light dimmers.\\+Up to 4 light dimmers can be connected to 1 HC. On sample plan we use 2 [[en:hiq_hw:ld-p4-iq|Light dimmers drivers]] for [[en:hiq_hw:lud12-iq|LUD-12]] universal light dimmers.\\
 \\ \\
 {{hiq_building_automation:hiq_home:methods:designing:designing07.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing07.png?nolink&800}}\\
  
 ===== Page 8 – CS - Blinds controllers  ===== ===== Page 8 – CS - Blinds controllers  =====
-Up to 2 [[en:hiq_home:hardware:bc-5-iq|Blinds controllers (BC)]] can be connected to 1 HC.\\+Up to 2 [[en:hiq_hw:bc-5-iq|Blinds controllers (BC)]] can be connected to 1 HC.\\
 \\ \\
 {{hiq_building_automation:hiq_home:methods:designing:designing08.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing08.png?nolink&800}}\\
Line 41: Line 41:
  
 ===== Page 9 – CS - bus extender, LED light dimmer ===== ===== Page 9 – CS - bus extender, LED light dimmer =====
-[[en:hiq_home:hardware:cad-be-prot-iq| Bus extender (BE)]] is a passive switch for easy IEX bus interconnection between cabinet and field modules.\\+[[en:hiq_hw:cad-be-prot-iq| Bus extender (BE)]] is a passive switch for easy IEX bus interconnection between cabinet and field modules.\\
 \\ \\
 Up to 4 light dimmers can be connected to 1 HC. On sample plan we use 2 [[en:hiq_home:hardware:ld-v4-iq|LED stripe dimmers]].\\ Up to 4 light dimmers can be connected to 1 HC. On sample plan we use 2 [[en:hiq_home:hardware:ld-v4-iq|LED stripe dimmers]].\\
Line 48: Line 48:
  
 ===== Page 10 – CS - Scene controllers  ===== ===== Page 10 – CS - Scene controllers  =====
-Up to 4 Scene Controllers can be connected to 1 HC. On sample plan are 4 [[en:hiq_home:hardware:sc-4t-iq|Scene Touch Panels]], but also  [[en:hiq_home:hardware:sc-4o-iq|Scene Panels]] and  [[en:hiq_home:hardware:sc-4s-iq|Scene controllers]] can be connected in the same way.\\+Up to 4 Scene Controllers can be connected to 1 HC. On sample plan are 4 [[en:hiq_hw:sc-4t-iq|Scene Touch Panels]], but also  [[en:hiq_hw:sc-4o-iq|Scene Panels]] and  [[en:hiq_hw:sc-4s-iq|Scene controllers]] can be connected in the same way.\\
 \\ \\
 {{hiq_building_automation:hiq_home:methods:designing:designing10.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing10.png?nolink&800}}\\
  
 ===== Page 11-12 -  CS - Thermostats  ===== ===== Page 11-12 -  CS - Thermostats  =====
-Up to 5 Thermostats can be connected to 1 HC. On sample plan we use 5 [[en:hiq_home:hardware:th-1t-iq|Touch buttons electronic thermostats]], but also ordinary  [[en:hiq_home:hardware:th-1m-iq|Electronic thermostats]] and  [[en:hiq_home:hardware:th-2-iq|Blind electronic thermostats]] can be connected in a similar way.\\+Up to 5 Thermostats can be connected to 1 HC. On sample plan we use 5 [[en:hiq_hw:th-1t-iq|Touch buttons electronic thermostats]], but also ordinary  [[en:hiq_hw:th-1m-iq|Electronic thermostats]] and  [[en:hiq_hw:th-2-iq|Blind electronic thermostats]] can be connected in a similar way.\\
 \\ \\
-Optionally we can connect window switch on each thermostat (sample on –TH02 and -TH03) (not possible with [[en:hiq_home:hardware:th-2-iq|Blind electronic thermostat]]).\\+Optionally we can connect window switch on each thermostat (sample on –TH02 and -TH03) (not possible with [[en:hiq_hw:th-2-iq|Blind electronic thermostat]]).\\
 \\ \\
 {{hiq_building_automation:hiq_home:methods:designing:designing11.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing11.png?nolink&800}}\\
Line 63: Line 63:
  
 ===== Page 13 -  CS-Fan-coil  ===== ===== Page 13 -  CS-Fan-coil  =====
-Up to 5 [[en:hiq_home:hardware:fc-1-iq| Fan-coil controllers (FC)]] can be connected to 1 HC. On our sample plan we have 3 FC, 2 thermostats are controlling radiator valves ([[en:hiq_home:methods:design#page_36-38_fan-coil|page 36-38]]).\\+Up to 5 [[en:hiq_hw:fc-1-iq| Fan-coil controllers (FC)]] can be connected to 1 HC. On our sample plan we have 3 FC, 2 thermostats are controlling radiator valves ([[en:hiq_home:methods:design#page_36-38_fan-coil|page 36-38]]).\\
 \\ \\
 FC controllers are the last items on IEX bus. Longer IEX bus lines (over 100m) must be terminated with a 120ohm resistor between CANL and CANH (-R1).\\ FC controllers are the last items on IEX bus. Longer IEX bus lines (over 100m) must be terminated with a 120ohm resistor between CANL and CANH (-R1).\\
Line 76: Line 76:
  
 ===== Page 15 – Home controller inputs ===== ===== Page 15 – Home controller inputs =====
-If used, optional [[en:hiq_home:hardware:rhkf-u| lightness sensor]] must be connected to IW0 analog input on [[en:hiq_home:hardware:hc-iq|home controller]]. \\+If used, optional [[en:hiq_hw:rhkf-u| lightness sensor]] must be connected to IW0 analog input on [[en:hiq_hw:hc-iq|home controller]]. \\
 All other inputs are left for custom programming solutions (10 digital inputs IX0-IX7, IX8A, IX9B  and 3 8-bit analog inputs IW1-IW3).\\ All other inputs are left for custom programming solutions (10 digital inputs IX0-IX7, IX8A, IX9B  and 3 8-bit analog inputs IW1-IW3).\\
 \\ \\
Line 83: Line 83:
 ===== Page 16 – Home controller outputs ===== ===== Page 16 – Home controller outputs =====
 QX0-QX4 outputs – can be used for radiator valves or to control other heating/cooling devices. Internal relay is used for valves, other loads are recommended to use an additional 16A installation relay.\\ QX0-QX4 outputs – can be used for radiator valves or to control other heating/cooling devices. Internal relay is used for valves, other loads are recommended to use an additional 16A installation relay.\\
-In our plan we use 2 radiator valves (and 3 [[en:hiq_home:hardware:fc-1-iq| Fan-coil controllers]]).\\+In our plan we use 2 radiator valves (and 3 [[en:hiq_hw:fc-1-iq| Fan-coil controllers]]).\\
 QX5 output – is used for Air Conditioner.\\ QX5 output – is used for Air Conditioner.\\
 QX6 output – is used for Boiler.\\ QX6 output – is used for Boiler.\\
Line 114: Line 114:
  
 ===== Page 28-29 – Light dimmers  ===== ===== Page 28-29 – Light dimmers  =====
-On sample plan we use 2 [[en:hiq_home:hardware:ld-p4-iq|Light dimmers drivers]]. On each driver we can connect up to 4 [[en:hiq_home:hardware:lud12-iq|LUD-12]] universal light dimmers.\\+On sample plan we use 2 [[en:hiq_hw:ld-p4-iq|Light dimmers drivers]]. On each driver we can connect up to 4 [[en:hiq_hw:lud12-iq|LUD-12]] universal light dimmers.\\
 \\ \\
 {{hiq_building_automation:hiq_home:methods:designing:designing28.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing28.png?nolink&800}}\\
Line 120: Line 120:
  
 ===== Page 30-33 – Blinds controllers  ===== ===== Page 30-33 – Blinds controllers  =====
-On our sample plan we have 2  [[en:hiq_home:hardware:bc-5-iq|Blinds controllers (BC)]] with 9 blinds and 9 double-push buttons.\\+On our sample plan we have 2  [[en:hiq_hw:bc-5-iq|Blinds controllers (BC)]] with 9 blinds and 9 double-push buttons.\\
 \\ \\
 {{hiq_building_automation:hiq_home:methods:designing:designing30.png?nolink&800}}\\ {{hiq_building_automation:hiq_home:methods:designing:designing30.png?nolink&800}}\\
Line 136: Line 136:
  
 ===== Page 36-38 – Fan-coil  ===== ===== Page 36-38 – Fan-coil  =====
-[[en:hiq_home:hardware:fc-1-iq|Fan-coil]] connection.\\+[[en:hiq_hw:fc-1-iq|Fan-coil]] connection.\\
 \\ \\