Line 11: Line 11:
 <WRAP column 600px> <WRAP column 600px>
  
-| Model number: ^ MC-24-01  | 24 VAC, 11 IO, Enocean, 2 × RS232, RS485, IEX2 terminals                 | +| Model number: ^ MC-24-05  | 24 VDC, 11 IO, 2 × RS232, RS485, IEX2 terminals                         | 
-| :::           ^ MC-24-02  | 24 VAC, 11 IO, 2 × RS232, RS485, IEX2 terminals                          | +| :::           ^ MC-24-06  | 24 VDC, 11 IO, 2 × RS232, RS485, IEX2 terminals, EnOcean                | 
-| Mounting:     | DIN rail, 6M, 106mm                                                                 ||+| Mounting:     | DIN rail(35mm), 6M, 106mm                                                                 ||
 | Dimensions:   | 106x108x58mm                                                                        || | Dimensions:   | 106x108x58mm                                                                        ||
  
Line 22: Line 22:
  
 ===== Features ===== ===== Features =====
- +  
-    * Sources and consumers measurements: +  * 12 digital inputs 
-      * 1 × Grid +  * 10 relay outputs 8 A 
-      * 3 × Local power plants (PV, wind, cogeneration,...) +  * 4 universal inputs/outputs 
-      * 2 × Storage system (battery) +  * Ethernet, USB, IEX-2, 2×RS232 
-      * 4 × Consumers +  * Enocean gateway (optional) 
-    * Load management +  * 24 VDC power supply   
-      * 4 × Consumers +
-      * Manual control +
-      * Manual override timer +
-      * Weekly timetable, 15 min resolution+
  
 ===== Safety standards ===== ===== Safety standards =====
  
-EN 50081-1, EN 61000-6-2, EN 61131-1, EN 61131-2, EN 61000-3-2, EN 61000-3-3+EN 61010-1, EN 61010-2-201, EN 61131-2
  
 <WRAP pagebreak></WRAP> <WRAP pagebreak></WRAP>
Line 42: Line 38:
 ===== Technical specification ===== ===== Technical specification =====
  
-|< 35% 40% >| +|< 42% 45% >| 
-| Relay outputs:               |                                    8A/250V | +| System clock                 |                               100MHz| 
-| Communication:               |    Ethernet, 2x RS232, 1x RS485, IEX-2 bus | +| Instruction execution        |                      10ns per instruction | 
-| Nominal power rating:        |                                     24 VDC | +| Program memory               |                    896Kb for user program | 
-| Power consumption:           |                  typ. 1W (no load), 10W max| +| Data memory                  |                    64Kb for user variables| 
-| Ingress protection:          |                                       IP20 | +| Data retention               |                                    7 days | 
-| Operating temperature:       |                                    0..45°C | +| RTC accuracy                 |               typ. ±2 sec per day at 25°C | 
-| Storage temperature:         |                                  -20..75°C | +| Digital input (ix00..ix11)   |     24V 7mA, opto isolated, bidirectional | 
-| Relative humidity:           |                                 0..95% n/c |+| Digital input (ix12..ix15)   |     dry contact, internal pull-up 12V 3mA | 
 +| Digital output (qx00..qx09)  |      relay 8A/250VAC or 8A/30VDC resistive| 
 +| Digital output (qx12..qx15)  |     NPN transistor 30V 1A| 
 +| IEX-2 bus load               |     48 modules (Cybro + 47 IEX-2)| 
 +| IEX-2 baud rate              |     20, 50, 100 (default), 250, 500kbps| 
 +| IEX-2 cable length, 100kbps  |     100m (non-terminated)| 
 +| IEX-2 cable length, 100kbps  |     300m (terminated)| 
 +| IEX-2 cable length, 50kbps   |     500m (terminated)| 
 +| Power supply                 |     24V (18..28V)| 
 +| Power consumption            |  50mA (no load), 180mA (10 relays, 4x 10Vout)| 
 +| Power output (IEX-2)         |     24V 2A (limited by resettable fuse)| 
 +| Operating conditions         |     0..50°C, 0..85% rh non-condensing| 
 +| Degree of protection         |     IP20| 
 +| Installation category        |     III|
  
 ===== Terminals ===== ===== Terminals =====
  
 +{{en:hiq_hw:pasted:mc-24-05terminals.png}}