User Tools

Site Tools


en:hiq_hw:pm3-e-d

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Next revision
Previous revision
en:hiq_hw:pm3-e-d [2022/11/30 08:54] – created gdzampoen:hiq_hw:pm3-e-d [2022/12/09 08:58] (current) saso_santelj
Line 5: Line 5:
 <WRAP column 350px> <WRAP column 350px>
  
-{{  :hiq_energy:hems:hardware:pm3-e-d_ct.png?nolink  |}}+{{  hiq_hardware:pm3-e-d_picture.png?nolink  |}}
  
 </WRAP> </WRAP>
Line 11: Line 11:
 <WRAP column 300px> <WRAP column 300px>
  
-| Model number: ^ PM3-E-D-CT                                   |+| Model number: ^ PM3-E-D                                   |
 | Connect to:   | [[en:hiq_hw:mc-230|MC-230]]           | | Connect to:   | [[en:hiq_hw:mc-230|MC-230]]           |
 | :::           | RS485 power sensor bus A - B                 | | :::           | RS485 power sensor bus A - B                 |
 | Mounting:     | DIN rail, 1M, 18 mm                          | | Mounting:     | DIN rail, 1M, 18 mm                          |
-| Dimensions:   65 × 72 × 94,5 mm                             +| Dimensions:   66 × 72 × 100 mm                             
  
 ^ Used for measuring power and energy of                 || ^ Used for measuring power and energy of                 ||
Line 31: Line 31:
 ===== Features ===== ===== Features =====
  
-  * DIN rail mounting with 3x current transformers ([[en:hiq_hw:ct-3-e-xx|3-ph current transformer]]+  * DIN rail mounting 
-  * Line voltage and THD% (total harmonic distortionof all phases+  * Three Phase 100A Direct Fed 
 +  * Accuracy Class 0.5 (Active Energy
 +  * Bi-directlonal Measurement for kW and kWh 
 +  * Configurable Pulsed output (Import/ Export/Nett kWh)
   * Line Frequency   * Line Frequency
-  * Currents, Current demands and current THD% of all phases 
   * Power, maximum power demand and power factor   * Power, maximum power demand and power factor
   * Active energy imported and exported   * Active energy imported and exported
   * Reactive energy imported and exported   * Reactive energy imported and exported
 +  * Supported Modbus
 +
 +
  
 ===== General description ===== ===== General description =====
  
-The unit measures and displays the characteristics of three phase four wires(3p4wsupplies, including voltage, frequency, current, power, active and reactive energy, imported or exported+PM3-E-D measures and displays the characteristics of 1p2w, 3p3w and 3p4w supplies, including voltage, frequency, current, power, active and reactive energy, imported or exported, harmonic etcBi-directional measurement makes it an ideal choice for Solar PV measurementThe units support Max. 100A direct connectionsaving the cost and avoiding the trouble to connect external CTsTwo pulse outputs and 1 communication port (Modbus) are provided for remote monitoringThe unit has been approved to meet the requirements of EU Directive 2014/32/EU.
- Energy is measured in terms of kWhkVArhMaximum demand current can be measured over preset periods of up to 60minutes +
-In order to measure energy, the unit requires voltage and current inputs in addition to the supply required to power the product +
-The requisite current input(s) are obtained via current transformers (CT). +
-This power sensor can be configured to work with a wide range of CTs with 0.33V output, giving the unit a wide range of operation. Built-in interfaces provide pulse and RS485 Modbus RTU outputs. Configuration is password protected. +
-This power sensor can be powered from a separate auxiliary (AC or DC) supply. Alternatively, it can be powered from the monitored supply, where appropriate. +
 ===== Technical specifications ===== ===== Technical specifications =====
  
 |< 35% 40% >| |< 35% 40% >|
 ^ Technical Data                                                               || ^ Technical Data                                                               ||
-| Operating Humidity                                                    ≤ 75% |+| Operating Humidity                                                    ≤ 90% |
 | Storage Humidity                                                      ≤ 95% | | Storage Humidity                                                      ≤ 95% |
 | Operating Temperature          |                                -25°C - +50°C | | Operating Temperature          |                                -25°C - +50°C |
Line 58: Line 57:
 | Mounting                                               DIN rail (DIN 43880) | | Mounting                                               DIN rail (DIN 43880) |
 | Sealing                        |                                  IP51 Indoor | | Sealing                        |                                  IP51 Indoor |
-| Auxiliary supply voltage                                       Nominal ± 1% | +| Frequency                      |                                 50Hz or 60Hz |
-| Auxiliary supply frequency                                     Nominal ± 1% | +
-| Frequency                      |                            50Hz or 60Hz(±2%) |+
 | Power Consumption              |                                        ≤ 10W | | Power Consumption              |                                        ≤ 10W |
 ^ Accuracy                                                                     || ^ Accuracy                                                                     ||
-| Voltage, Current                                                       0.5% | +| Voltage, Current                                      0.2of range maximum 
-| Frequency                      |                        0.2% of Mid-Frequency |+| Frequency                      |                        0.1% of Mid-Frequency |
 | Power Factor                                             1% of Unity (0.01) | | Power Factor                                             1% of Unity (0.01) |
-| Active Power, Apparent Power                          ± 1% of Range Maximum | 
-| Reactive Power                                        ± 1% of Range Maximum | 
-| Reactive Energy (Varh)                                ± 1% of Range Maximum | 
-| Active Energy (Wh)                                      Class 1 IEC 62053-21| 
 ^ Current transformer                                                          || ^ Current transformer                                                          ||
 | Frequency                      |                                     50-60 Hz | | Frequency                      |                                     50-60 Hz |
-Rated current                                                          50 A | +Max current                    |                                        100 A |
-| Accuracy                                  from 20% to 120% of rated current | +
-| Phase angle                    |  less than 2 degrees at 50% of rated current | +
-| Insulation voltage                                                  600 VAC | +
-| Maximum primary voltage        |               5000 VAC (insulated conductor) | +
-| Dielectric strength            |                              2.5 kV/1mA/1min | +
-| Operating temperature          |                                  -15 to 60°C | +
-| Operating humidity                                                   < 85 % | +
-| Case material                  |                                   PC/UL94-V0 | +
-| Bobin                          |                                          PBT | +
-| Core                                                              Permalloy | +
-| Internal structure             |                                        Epoxy | +
-| Leads                          |                UL 1015, Twisted pair, 22 AWG |+
 ^ Modbus                                                                       || ^ Modbus                                                                       ||
-Bus Type                                                RS485 (Semi-Duplex|+Transmission Mode                                         RS485 Half-Duplex |
 | Protocol                                                         Modbus RTU | | Protocol                                                         Modbus RTU |
-| Baud Rate                      |                       1200/2400/4800/9600bps |+| Baud Rate                      |                           2400bps - 38400bps |
 | Address Range                  |                                        1-247 | | Address Range                  |                                        1-247 |
-| Max. Bus Loading                                                      64pcs | 
-| Communication Distance                                          1000 Meters | 
 | Parity                                                        EVEN/ODD/NONE | | Parity                                                        EVEN/ODD/NONE |
 | Data Bit                                                                  8 | | Data Bit                                                                  8 |
-| Stop Bit                                                                  1 |+| Stop Bit                                                              or 2|
                                                                                                  
                                                                                                  
-                                                 
-                                                 
-                                                 
-                                                 
-                                                 
-                                                 
-                                                 
-                                                 
-<WRAP pagebreak></WRAP> 
- 
-===== Dimensions ===== 
- 
-{{:hiq_energy:hems:hardware:pm3-e_ct_dimensions.png?nolink|}} 
- 
-===== Installation ===== 
- 
-{{:hiq_energy:hems:hardware:pm3-e_instalation.png?nolink|}} 
- 
-{{ :hiq_energy:hems:hardware:hiq_pm3-e-d-ct_user_manual_v1.pdf |}} {{ :hiq_energy:hems:hardware:hiq_pm3-e-d-ct_protocol_v1.6.pdf |}} 
  
 +<WRAP pagebreak></WRAP>                                                  
 +                                             
 +===== Installation & Dimensions =====
  
 +{{:hiq_hardware:sdm630-installation.png?nolink|}}
  
  
en/hiq_hw/pm3-e-d.1669798464.txt.gz · Last modified: 2022/11/30 08:54 by gdzampo