| ==== PV inverter ==== | ==== PV inverter ==== | ||
| - | Monitoring of PV Inverter | + | Obtaining relevant data from photovoltaic |
| - | 1. adding | + | 1. adding power-sensor to measure produced electricity |
| 2. connecting PV inverter by Modbus TCP to EVSE (only for SolarEdge inverters) | 2. connecting PV inverter by Modbus TCP to EVSE (only for SolarEdge inverters) | ||
| - | === One-phase sensor PM1-E-D | + | === EVSE and PV inverter connection |
| - | | + | |< 700px >| |
| - | * In HEMS Configurator power-sensor should appear as a "new device" | + | | {{ : |
| - | * Press and hold the push-button on the power-sensor until it appears **-SEt-** on display | + | |
| - | * In HEMS Configurator click on the **" add"** button next to the source or consumer that the sensor | + | To add inverter on HEMS configurator: |
| - | * | + | |
| + | * on io mux page set IP address for inverter. Please see [[en: | ||
| + | |||
| + | To setup Modbus TCP on Inverter using SetApp: | ||
| + | * Select Site Communication menu | ||
| + | * RS485-1 -> Protocol -> SunSpec (Non-SE Logger) | ||
| + | * RS485-1 -> Device ID, and enter the number 1 | ||
| + | * Modbus TCP and set to Enable | ||
| + | * set TCP port to 502 | ||
| + | |||
| + | **Note**:\\ The TCP server idle time is 2 minutes. In order to leave the connection open, the request should be made within 2 minutes.\\ It is important | ||