en:robotina_charger:commissioning:pv_inverter
Differences
This shows you the differences between two versions of the page.
| Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
| en:robotina_charger:commissioning:pv_inverter [2022/12/09 13:55] – [EVSE and PV inverter connection] gdzampo | en:robotina_charger:commissioning:pv_inverter [2022/12/09 14:59] (current) – [EVSE and PV inverter connection] gdzampo | ||
|---|---|---|---|
| Line 24: | Line 24: | ||
| To add inverter on HEMS configurator: | To add inverter on HEMS configurator: | ||
| - | * on settings page inside source table, select SolarEdge inverter. [[en: | + | * on settings page inside source table, select SolarEdge inverter. |
| - | * on io mux page define | + | * on io mux page set IP address for inverter. |
| To setup Modbus TCP on Inverter using SetApp: | To setup Modbus TCP on Inverter using SetApp: | ||
| * | * | ||
| * RS485-1 -> Protocol -> SunSpec (Non-SE Logger) | * RS485-1 -> Protocol -> SunSpec (Non-SE Logger) | ||
| - | * RS485-1 -> Device ID, and enter the number 1. | + | * RS485-1 -> Device ID, and enter the number 1 |
| - | | + | * Modbus TCP and set to Enable |
| - | | + | |
| - | | + | |
| - | + | **Note**:\\ The TCP server idle time is 2 minutes. In order to leave the connection open, the request should be made within 2 minutes.\\ It is important to follow rules above, firstly to set HEMS configurator following Inverter setup due to 2 minutes time frame. | |
| - | *TCP port is 1502 by default. | + | |
en/robotina_charger/commissioning/pv_inverter.1670594124.txt.gz · Last modified: by gdzampo