====== Manufacture ====== ===== MC-230 ===== Upload FW: {{ :hiq_energy:hems:methods_resources:hems_v1.0.2.cyp | FW HEMS v1.0.2}} ===== Power-sensors ===== Modbus settings for supplied power-sensors: **9600 8n2; ID: 149** ==== PM1-E-D and PM3-E-D ==== Factory setting: **2400 8n1; ID: 1; Ct: 5** Put power-sensor (PM1-E-D) in set mode by pressing button until **-SET-** is displayed on power-sensor display. | Parameter | Address (hex) | Format | Default value (hex) | New value (hex) | | Parity / Stop bits | 40019 (00 12) | float | 0 (00 00 00 00) = n1 | 3 (40 40 00 00) = n2 | | Sensor ID | 40021 (00 14) | float | 1 (3F 80 00 00) = 1 | 149 (43 15 00 00) = 149 | | Baud Rate | 40029 (00 1C) | float | 0 (00 00 00 00) = 2400 | 2 (40 00 00 00) = 9600 | | Ct- Primary cuurent| 40051 (00 32) | float | 5 (40 A0 00 00) = 5 | 50 (42 48 00 00) = 50 or 100 (42 C8 00 00) = 100 | CyBro-2-230-E configuring SW: {{ :hiq_energy:hems:methods_resources:eastron_config.zip |}} ==== PM3-I-D ==== Power-meters are supplied according to our specifications - no configuration needed before sending.