====== Manual HIQ device controllers address ====== Download, unzip and run CybroIEXManager {{hiq_building_automation:hiq_home:sw:cybroiexmanager.zip|CyBroIexManager}}. Pres "Scan" button [1] to discover all controllers in LAN. Select HC-IQ serial number on discovered controllers list [2] and press "Scan IEX" button [3]. All HIQ-DC should appear in main list-box [4]. {{hiq_building_automation:hiq_home:sw:configurator:manual_address:iex_manager_1.png?direct&300|}} {{hiq_building_automation:hiq_home:sw:configurator:manual_address:iex_manager_2.png?direct&300|}} In "New NAD" column [5] enter NAD addresses as per following table: |<30% 20% 20% 20% >| ^ HIQ-DC ^ order ^ address | ^ LC-10-IQ | 1st | 100 | ^ ::: | 2nd | 101 | ^ ::: | 3rd | 102 | ^ ::: | 4th | 103 | | ||| ^ LD-X4-IQ* | 1st | 120 | ^ ::: | 2nd | 121 | ^ ::: | 3rd | 122 | ^ ::: | 4th | 123 | | ||| ^ BC-5-IQ | 1st | 200 | ^ ::: | 2nd | 201 | | ||| ^ SC-4X-IQ | 1st | 300 | ^ ::: | 2nd | 301 | ^ ::: | 3rd | 302 | ^ ::: | 4th | 303 | | ||| ^ TH-X-IQ | 1st | 400 | ^ ::: | 2nd | 401 | ^ ::: | 3rd | 402 | ^ ::: | 4th | 403 | ^ ::: | 5th | 404 | | ||| ^ FC-1-IQ | 1st | 420 | ^ ::: | 2nd | 421 | ^ ::: | 3rd | 422 | ^ ::: | 4th | 423 | ^ ::: | 5th | 424 | * LD-D8-IQ is detected as two separate modules. And press "Send" button [6]. **Note: If we press "Autoaddress" then the manual address will be corrupted and must be repeated.**