====== 12 temperature sensor inputs ======
**IEX-2 temperature measurement module with 12 Pt1000 inputs**
{{ hiq_energy:goflex_hems:hardware:air12.png?nolink |}}
| Model number: ^ AIR-12 |
| Mounting: | DIN rail, 3M |
| Dimensions: | 53x117x58mm |
^ Compatible sensors: ||
| Pt1000 temperature probe | [[en:hiq_hw:s-pt1000|S-PT1000]] |
===== Applications =====
* temperature measurements
===== Technical specification =====
|< 60% 40% >|
| Number of i/o points | 12 analog inputs |
| Input type | software selectable (common for all inputs): |
| ::: | - Pt100/1000 (DIN751), measuring range -100..300°C |
| ::: | - Ni100/1000 (DIN43760), measuring range -50..160°C |
| ::: | - Ni100/1000 (Landis & Gyr), measuring range -50..160°C |
| ::: | - potentiometer 0..2000 ohm |
| Connection type | 2-wire or 3-wire |
| Wire resistance | 20 ohm max. (3-wire mode) |
| A/D converter | V/f conversion with auto calibration |
| Accuracy | 0.1% of measuring range |
| Resolution | 14 bits (input modes with 0.1% accuracy) |
| ::: | 12 bits (input modes with 0.5%/1% accuracy) |
| Sensor current | 0.2mA (each sensor) |
| Temperature drift | +/-0.01%/°C of measuring range |
| Scan time | 30ms..1120ms, depends on input mode |
| Integration time | 20ms or 60ms, depends on input mode |
| Calibration reference | 150.00 ohm, 1500.0 ohm |
| Accuracy, scan time | software selectable, depends on input mode |
| Power supply | 24V (19..28V), 50mA |
| Galvanic isolation | 1kV between digital and analog circuit no isolation between channels |
| IEX-2 baud rate | 20, 50, 100, 250, 500kbps, auto selectable |
| Operating conditions | 0..50°C, 0..85% rh non-condensing |
| Mounting | DIN rail (35mm) |
| Dimension | 53x117x58mm |
| Weight gross | 160g |
| Enclosure protection | IP20 |
| Level of ambient pollution | 2 |
| Standards | EN 61131-1, EN 61131-2, EN 50090-2-2 |
===== Wiring =====
{{hiq_energy:goflex_hems:hardware:air12_wiring.png?nolink |}}