====== Single phase power-sensor, CT ====== **1-phase power-sensor, current transformer** {{ :hiq_energy:hems:hardware:pm1-e-d-ct.png?nolink |}} | Model number: ^ PM1-E-D-CT | | Connect to: | [[en:hiq_hw:mc-230|MC-230]] | | ::: | RS485 power sensor bus A - B | | Mounting: | DIN rail, 1M, 18 mm | | Dimensions: | 18 × 62 × 119 mm | ^ Used for measuring power and energy of || | ✔ | single-phase energy sources | | ✔ | single-phase energy consumers | ===== Applications ===== * Digital multi-function power sensor for single phase networks ===== Features ===== * DIN rail mounting with 50A current transformer ([[en:hiq_hw:ct1-e-50|1-ph current transformer]] ) * Compact design in a single module 18mm wide * Seal-able cover(phase and neutral terminals) ===== General description ===== The PM1-E-D series is an advanced single phase energy monitoring solution with built-in configuration push button and LCD data display. Particularly indicated for metering active energy and other power parameters. Housing for DIN-rail mounting, IP51 protection degree. ===== Technical specifications ===== |< 35% 40% >| ^ Technical Data || | Operating Humidity | ≤ 75% | | Storage Humidity | ≤ 95% | | Operating Temperature | -20°C - +50°C | | Storage Temperature | -30°C - +70°C | | International Standard | IEC 62053-21 | | Accuracy | Class 1 | | Mounting | DIN rail (DIN 43880) | | Sealing | IP51 Indoor | | Nominal Voltage Input | (Ph+N) 230V AC (176-276V AC) | | Max Continuous Voltage | 120% of nominal | | AC Voltage Withstand | 4KV for 1 minute | | Impulse Voltage Withstand | 6KV-1.2μS | | Current Input | 0.25-5A(6)A AC RMS | | Operational Current Range | 0.4% Ib-Imax | | Over current withstand | 20Imax for 0.01s | | Nominal Input Current Burden | 0.5VA | | Frequency | 50Hz(±10%) | | Power Consumption | ≤ 2W/10VA/phase | ^ Accuracy || | Voltage, Current | 0.5% | | Frequency | 0.2% of Mid-Frequency | | Power Factor | 1% of Unity (0.01) | | Active Power, Apparent Power | ≤ 1% of Range Maximum | | Reactive Power | ≤ 1% of Range Maximum | | Reactive Energy (Varh) | Class 2 | | Active Energy (Wh) | Class 1 | ^ Current transformer || | Frequency | 50-60 Hz | | Rated current | 50 A | | Accuracy | from 20% to 120% of rated current | | Phase angle | less than 2 degrees at 50% of rated current | | Insulation voltage | 600 VAC | | Maximum primary voltage | 5000 VAC (insulated conductor) | | Dielectric strength | 2.5 kV/1mA/1min | | Operating temperature | -15 to 60°C | | Operating humidity | < 85 % | | Case material | PC/UL94-V0 | | Bobin | PBT | | Core | Permalloy | | Internal structure | Epoxy | | Leads | UL 1015, Twisted pair, 22 AWG | ^ Modbus || | Bus Type | RS485 (Semi-Duplex) | | Protocol | Modbus RTU | | Baud Rate | 1200/2400/4800/9600bps | | Address Range | 1-247 | | Max. Bus Loading | 64pcs | | Communication Distance | 1000 Meters | | Parity | EVEN/ODD/NONE | | Data Bit | 8 | | Stop Bit | 1 | ===== PM1-E-D-CT Terminals ===== {{:hiq_energy:hems:hardware:pm1_ct_terminals.png?nolink|}} {{ :hiq_energy:hems:hardware:hiq_pm1-e-d-ct_user_manual_2020_v1.0.pdf |}} {{ :hiq_energy:hems:hardware:hiq_pm1-e-d-ct_protocol_v1.2.pdf |}}