====== Three phase power-sensor ======
**Three phase power-sensor**
{{ hiq_energy:goflex_hems:hardware:pm3-i-d.png?nolink&250 |}}
| Model number: ^ PM3-I-D |
| Connect to: | [[en:hiq_hw:mc-230|MC-230]] |
| ::: | RS485 power sensor bus A - B |
| Mounting: | DIN rail, 3M, 53 mm |
| Dimensions: | 53 × 84 × 66 mm |
^ Used for measuring power and energy of ||
| ✔ | three-phase energy sources |
| ✔ | three-phase energy consumers |
===== Applications =====
* Digital multi-function power-sensor for 3-phase sources or consumers
===== Features =====
* Three phase direct connection up to 65 A
* Serial RS485 communication
* Display LCD 7+1 digit
* Multi-functional front LED
===== General description =====
The PM-3-IQ is intended for energy measurements in three-phase electrical power network and can be used in residential, industrial and utility applications. Power-sensor measures energy directly in 4-wire networks according to the principle of fast sampling of voltage and current signals.
Connecting terminals can be sealed up against non-authorized access with protection covers. They are built to be fastened according to EN 60715 standard. Power-sensor has built-in RS485 serial communication with the MODBUS protocol which enables data transmission and thus connection of the measuring places into the network for the control and management with energy.
===== Technical specifications =====
|< 35% 40% >|
| Nominal voltage | 3x230/400 VAC (-20..+15%) |
| Power connector | 1,5 .. 16 mm2 |
| Reference current | 5 A |
| Maximum current | 65 A |
| Operational frequency range | 50 or 60 Hz|
| Internal power consumption | < 8 VA |
| Communication type | RS485(half-duplex) |
| Communication protocol | Modbus RTU |
^ Accuracy ||
| Active energy (Wh) | Class 1 IEC 62053-21 |
| ::: | class B EN 50470-3 |
| ::: | ±1.5% from Imin to Itr |
| ::: | ±1% from Itr to Imax |
^ Ambient conditions and Safety ||
| Dust/water protection | IP50 |
| Operating temp. range | -25 ... 55°C |
| Indoor sensor | yes |
| Protection class | II |
^ EC Directives conformity ||
| EC Directive on Measuring Instruments 2014/32/EU ||
| EC Directive on EMC 2014/30/EU ||
| EC Directive on Low Voltage 2014/35/EU ||
| EC Directive WEEE 2002/96/EC ||
===== Connection =====
{{:hiq_energy:hems:hardware:pm3_terminals.png?nolink |}}
===== Manual =====
{{ hiq_energy:goflex_hems:hardware:wm3-6-tehnicna-dokumentacija-ver-1.04.pdf | PM3-I-D Technical Documentation}}