====== Wireless Modbus Relay ======
**Wireless Modbus Relay**
{{ hiq_hardware:wr-1_base.png?nolink&0x500 }}
| Model number: ^ WR-1 |
| Frequency: | ISM 868MHz (EU) |
| Dimensions: | 93x45x27 mm |
===== Applications =====
* Remote controlled relay. Act as modbus RTU slave. Optimal for long range, no hopping.
===== Installation and mounting =====
* :!: Carefully open WR-1 module and configure address with jumpers. (Default address is 200)
* :!: Place WR-1 module at least 10cm from other objects. Installation is not recommended inside metal cabinets.
* Connect relay terminals
* Connect to 230V power supply
* Configure radio pairing
{{ hiq_hardware:wr-1_wiring.png?nolink&0x500 }}
{{ hiq_hardware:wr-1_dimension.png?nolink&0x500 }}
===== Features =====
* remote controlled relay
* act as modbus RTU slave
* very long range, no hopping
* up to 8 relays per network
* protected private connection
* multiple addressable groups
===== Technical specification =====
| Power supply: | 230V, 50/60Hz, 1W |
| Ingress protection: | IP20 |
| Operating temperature: | -20..50°C |
| Storage temperature: | -40..85°C |
| Relative humidity: | 0..85% n/c |
Modbus
| Address range: | 200..207 |
| Relay mapping | coil 1(start address 00h) |
| Data bits & parity | 8n1 |
| Supported functions | 01 - read coil \\ 05 - write single coil \\ 15 - write multiple coils |
Relay output
| Nominal rating | 10A 250Vac (NO), 3A 250Vac (NC) |
| (resistive) | 5A 30Vdc (NO), 3A 30Vdc (NC) |
Radio
|Frequency band | ISM 868MHz (EU) |
|Subband | L 866.8MHz, 25mW, 1% utility |
|Modulation | fSK 38.4kbps 80kHz bandwidth |
|Listen before talk | yes, delay limited to 20ms |
|Group address | 32-bit, automatically generated |
|Connection time | 10s power-on to network ready |
|Message delay | 5ms from tx start to relay on |
|Output power | 25mW |
|Operating range | 3..300m with optical visibility|
===== Modbus address setting =====
Change is applied right away, no reset needed.
{{ hiq_hardware:WR-1_address_settings.png?nolink&0x500 }}
===== Radio pairing configuration =====
==== Create new secure group ====
* turn on all devices as the same time
* within 10 seconds, while RF LED is blinking, press and hold button on one of the devices
* after a second, the new address is randomly generated and sent to all devices. RF LED will blink 3 times to confirm the new address.
{{ hiq_hardware:wm1_configuration_1.png?nolink&0x500 }}
==== Add new device to the group ====
* turn on the device
* within 10 seconds, press and hold button on one of the existing devices
* after a second, the existing group address is sent to the new device. RF LED will blink 3 times to confirm the address is sent.
{{ hiq_hardware:wm1_configuration_2.png?nolink&0x500 }}
==== Examples ====
{{ hiq_hardware:WR-1_examples.png?nolink&0x300 }}
===== Connection check =====
* press the button shortly \\
With each press of the button, the relay will
switch on/off. Other devices are not affected.
{{ hiq_hardware:WR-1_relay_button.png?nolink&0x150 }}
===== Factory reset =====
* Hold button and turn the device ON
* RF led will blink twice. Group address is now reset to default.
* Other devices will not be affected.
{{ hiq_hardware:wm1_factoryreset.png?nolink&0x200 }}