Table of Contents

Manufacture

MC-230

Upload FW: FW HEMS v1.0.2

Power-sensors

Modbus settings for supplied power-sensors: 9600 8n2; ID: 149

PM1-E-D and PM3-E-D

Factory setting: 2400 8n1; ID: 1; Ct: 5

Put power-sensor (PM1-E-D) in set mode by pressing button until -SET- is displayed on power-sensor display.

Parameter Address (hex) Format Default value (hex) New value (hex)
Parity / Stop bits 40019 (00 12) float 0 (00 00 00 00) = n1 3 (40 40 00 00) = n2
Sensor ID 40021 (00 14) float 1 (3F 80 00 00) = 1 149 (43 15 00 00) = 149
Baud Rate 40029 (00 1C) float 0 (00 00 00 00) = 2400 2 (40 00 00 00) = 9600
Ct- Primary cuurent 40051 (00 32) float 5 (40 A0 00 00) = 5 50 (42 48 00 00) = 50 or 100 (42 C8 00 00) = 100

CyBro-2-230-E configuring SW: eastron_config.zip

PM3-I-D

Power-meters are supplied according to our specifications - no configuration needed before sending.