en:goflex_hems:hardware:pm3-i-d
This is an old revision of the document!
Table of Contents
Three phase power-meter
Three phase power-meter
Model number: | PM3-I-D |
---|---|
Mounting: | DIN rail, 3M, 53 mm |
Dimensions: | 53 × 84 × 66 mm |
Used for measuring power and energy of | |
---|---|
✔ | three-phase energy sources |
✔ | three-phase energy consumers |
Applications
- Digital multi-function energy meter for or 3-phase sources or consumers
Features
- Three phase direct connection up to 80 A
- Serial RS485 communication
- Display LCD 7+1 digit
- Multi-functional front LED
General description
The PM-3-IQ is intended for energy measurements in three-phase electrical power network and can be used in residential, industrial and utility applications. Meter measures energy directly in 4-wire networks according to the principle of fast sampling of voltage and current signals.
Connecting terminals can be sealed up against non-authorized access with protection covers. They are built to be fastened according to EN 60715 standard. Meter has built-in RS485 serial communication with the MOD-BUS protocol which enables data transmission and thus connection of the measuring places into the network for the control and management with energy.
Technical specifications
Nominal voltage | 230 VAC (-20..+15%) |
Power connector | 2,5 .. 16 mm2 |
Reference current | 5 A |
Maximum current | 80 A |
Operational frequency range | 50 or 60 Hz |
Internal power consumption | < 8 VA |
Communication type | RS485(half-duplex) |
Communication protocol | Modbus RTU |
Accuracy | |
---|---|
Active energy (Wh) | Class 1 IEC 62053-21 |
class B EN 50470-3 | |
±1.5% from Imin to Itr | |
±1% from Itr to Imax | |
Ambient conditions and Safety | |
Dust/water protection | IP50 |
Operating temp. range | -25 … 55°C |
Indoor meter | yes |
Protection class | II |
EC Directives conformity | |
EC Directive on Measuring Instruments 2014/32/EU | |
EC Directive on EMC 2014/30/EU | |
EC Directive on Low Voltage 2014/35/EU | |
EC Directive WEEE 2002/96/EC |
Terminals
PM3-I-D | Power source | ||
---|---|---|---|
Phase 1 IN | L1↑ | 1 | L1 |
Phase 2 IN | L2↑ | 4 | L2 |
Phase 3 IN | L3↑ | 7 | L3 |
Neutral | N | 10 | N |
PM3-I-D | Power consumer | ||
---|---|---|---|
Phase 1 OUT | L1↑ | 3 | L1 |
Phase 2 OUT | L2↑ | 6 | L2 |
Phase 3 OUT | L3↑ | 9 | L3 |
Neutral | N | 11 | N |
PM3-I-D | CAD-232-A2-IQ | BR-WN-W | |
---|---|---|---|
RS485 | 16 | A | Rx/T+ |
15 | B | Tx/T- |
Connection
Manual