Three phase power-meter
Three phase power-meter
| Model number: | PM3-I-D |
|---|---|
| Mounting: | DIN rail, 3M, 53 mm |
| Dimensions: | 53 × 84 × 66 mm |
| Used for measuring power and energy of | |
|---|---|
| ✔ | three-phase energy sources |
| ✔ | three-phase energy consumers |
Applications
- Digital multi-function energy meter for or 3-phase sources or consumers
Features
- Three phase direct connection up to 65 A
- Serial RS485 communication
- Display LCD 7+1 digit
- Multi-functional front LED
General description
The PM-3-IQ is intended for energy measurements in three-phase electrical power network and can be used in residential, industrial and utility applications. Meter measures energy directly in 4-wire networks according to the principle of fast sampling of voltage and current signals.
Connecting terminals can be sealed up against non-authorized access with protection covers. They are built to be fastened according to EN 60715 standard. Meter has built-in RS485 serial communication with the MOD-BUS protocol which enables data transmission and thus connection of the measuring places into the network for the control and management with energy.
Technical specifications
| Nominal voltage | 3×230/400 VAC (-20..+15%) |
| Power connector | 1,5 .. 16 mm2 |
| Reference current | 5 A |
| Maximum current | 65 A |
| Operational frequency range | 50 or 60 Hz |
| Internal power consumption | < 8 VA |
| Communication type | RS485(half-duplex) |
| Communication protocol | Modbus RTU |
| Accuracy | |
|---|---|
| Active energy (Wh) | Class 1 IEC 62053-21 |
| class B EN 50470-3 | |
| ±1.5% from Imin to Itr | |
| ±1% from Itr to Imax | |
| Ambient conditions and Safety | |
| Dust/water protection | IP50 |
| Operating temp. range | -25 … 55°C |
| Indoor meter | yes |
| Protection class | II |
| EC Directives conformity | |
| EC Directive on Measuring Instruments 2014/32/EU | |
| EC Directive on EMC 2014/30/EU | |
| EC Directive on Low Voltage 2014/35/EU | |
| EC Directive WEEE 2002/96/EC | |
Terminals
| PM3-I-D | Power source | ||
|---|---|---|---|
| Phase 1 IN | L1↑ | 1 | L1 |
| Phase 2 IN | L2↑ | 4 | L2 |
| Phase 3 IN | L3↑ | 7 | L3 |
| Neutral | N | 10 | N |
| PM3-I-D | Power consumer | ||
|---|---|---|---|
| Phase 1 OUT | L1↑ | 3 | L1 |
| Phase 2 OUT | L2↑ | 6 | L2 |
| Phase 3 OUT | L3↑ | 9 | L3 |
| Neutral | N | 11 | N |
| PM3-I-D | CAD-232-A2-IQ | BR-WN-W | |
|---|---|---|---|
| RS485 | 16 | A | Rx/T+ |
| 15 | B | Tx/T- | |