User Tools

Site Tools


en:goflex_hems:methods_resources:manufacture

Manufacture

HC-IQ

GW-WN-W

Configure DIP SW to 1 = ON, 2 - 8 = OFF

Power-meters

Modbus settings for power-meters we supply: 9600 8n2; ID: 149

Eastron

Factory setting: 2400 8n1; ID: 1

Put power-meter in set mode by pressing button until -SET- is displayed on power-meter display.

Parameter Address (hex) Format Default value (hex) New value (hex)
Parity / Stop bits 40019 (00 12) float 0 (00 00 00 00) = n1 3 (40 40 00 00) = n2
Meter ID 40021 (00 14) float 1 (3F 80 00 00) = 1 149 (43 15 00 00) = 149
Baud Rate 40029 (00 1C) float 0 (00 00 00 00) = 2400 2 (40 00 00 00) = 9600

CyBro-2-230-E configuring SW: eastron_config.zip

Iskra

Power-meters are supplied according to our specifications - no configuration needed before sending.

AiR-12

Set NAD to 700

TS-H

Set NAD to 800 - 807

en/goflex_hems/methods_resources/manufacture.txt · Last modified: 2018/10/05 13:32 by goran.kocjancic