en:hiq_hw:air-12
This is an old revision of the document!
Table of Contents
12 temperature sensor inputs
IEX-2 temperature measurement module with 12 Pt1000 inputs
| Model number: | AIR-12 |
|---|---|
| Mounting: | DIN rail, 3M |
| Dimensions: | 53x117x58mm |
| Compatible sensors: | |
|---|---|
| Pt1000 temperature probe | S-PT1000 |
Applications
- temperature measurements
Technical specification
| Number of i/o points | 12 analog inputs |
| Input type | software selectable (common for all inputs): |
| - Pt100/1000 (DIN751), measuring range -100..300°C | |
| - Ni100/1000 (DIN43760), measuring range -50..160°C | |
| - Ni100/1000 (Landis & Gyr), measuring range -50..160°C | |
| - potentiometer 0..2000 ohm | |
| Connection type | 2-wire or 3-wire |
| Wire resistance | 20 ohm max. (3-wire mode) |
| A/D converter | V/f conversion with auto calibration |
| Accuracy | 0.1% of measuring range |
| Resolution | 14 bits (input modes with 0.1% accuracy) |
| 12 bits (input modes with 0.5%/1% accuracy) | |
| Sensor current | 0.2mA (each sensor) |
| Temperature drift | +/-0.01%/°C of measuring range |
| Scan time | 30ms..1120ms, depends on input mode |
| Integration time | 20ms or 60ms, depends on input mode |
| Calibration reference | 150.00 ohm, 1500.0 ohm |
| Accuracy, scan time | software selectable, depends on input mode |
| Power supply | 24V (19..28V), 50mA |
| Galvanic isolation | 1kV between digital and analog circuit no isolation between channels |
| IEX-2 baud rate | 20, 50, 100, 250, 500kbps, auto selectable |
| Operating conditions | 0..50°C, 0..85% rh non-condensing |
| Mounting | DIN rail (35mm) |
| Dimension | 53x117x58mm |
| Weight gross | 160g |
| Enclosure protection | IP20 |
| Level of ambient pollution | 2 |
| Standards | EN 61131-1, EN 61131-2, EN 50090-2-2 |
Wiring
en/hiq_hw/air-12.1565779793.txt.gz · Last modified: by goran.kocjancic