en:hiq_hw:ts-h
Table of Contents
Temperature and humidity sensor
Room temperature and humidity sensor
| Model number: | TS-H |
|---|---|
| Mounting: | on-wall |
| Dimensions: | 71×71×27mm |
| Require: | |
|---|---|
| IEX-2 bus expander | CAD-BE-PROT-IQ |
| Compatible external sensors: | |
|---|---|
| ES temperature probe | ES |
Applications
- room temperature and humidity measurements
Technical specification
| Temperature measurement | internal and external |
| range: 0°C to +50°C | |
| error: max. ±2°C (0°C to +50°C) | |
| typ. ±0.5°C (0°C to +50°C, backlight at 20%) | |
| resolution: 0.1°C (12 bit) | |
| readout: 0.1°C (254 equals 25.4°C) | |
| Humidity measurement | internal |
| range: 0..100% rh, non-condensing | |
| error: ±2% rh @ 25°C | |
| response time 15s | |
| stability ±1% rh @ 50% rh in 5 years | |
| resolution 1% (7 bit) | |
| readout 1% rh (45 equals 45% rh) | |
| Power consumption | 24V (18..26V), 15mA |
| IEX-2 baud rate | 20, 50, 100, 250, 500kbps, auto selectable |
| Degree of protection | IP20 |
| Operating conditions | 0..50°C, 0..85% rh non-condensing |
| Storage temperature | -20..75°C |
| Mounting | wall surface |
| Dimension | 71x71x27mm |
| Weight gross | 100g |
| Level of ambient pollution | 2 |
| Standards | EN 61000-6-2, EN 61000-6-3 |
Terminals
| TS-H | ||
|---|---|---|
| GND | BE-PROT-IQ | GND |
| CANL | CANL | |
| CANH | CANH | |
| +24V | +24V | |
| TS0 | ES | red |
| GND | black | |
en/hiq_hw/ts-h.txt · Last modified: by goran.kocjancic