Power sensor management
Default address on all power sensor is 149.
Available addresses for sensors are listed in table.
Address | Power sensor position |
---|---|
149 | Default |
150 | Grid |
154,155,156 | PV |
157,158 | Battery storage |
161..167 | Consumer |
Add power sensor procedure:
- wire it to communication bus,
- only for PM1-E-D: press and hold the push-button on the power sensor until it appears -SEt- on display,
- it should appear in configurator as new device, click on button add next to the source or consumer where sensor should be assigned,
- repeat procedure for next.
Note 1: Adding of power sensor is supported one by one.
Note 2: PM3-E-D supports address setting manually on its display before adding it to communication bus.
Del power sensor procedure:
- make sure new device is empty,
- only for PM1-E-D: press and hold the push-button on the power sensor until it appears -SEt- on display,
- press del button next to the sensor,
- after a few seconds, the sensor should appear as the new device (as on image above),
- sensor can be physically removed or it can be assigned to another device.
Without grid power sensor
- Virtual grid PS is an option if no grid meter is used. Power, current and energy will be calculated from other power sensors.