en:hems:methods_resources:manufacture
Table of Contents
Manufacture
MC-230
Upload FW: FW HEMS v1.0.2
Power-sensors
Modbus settings for supplied power-sensors: 9600 8n2; ID: 149
PM1-E-D and PM3-E-D
Factory setting: 2400 8n1; ID: 1; Ct: 5
Put power-sensor (PM1-E-D) in set mode by pressing button until -SET- is displayed on power-sensor display.
Parameter | Address (hex) | Format | Default value (hex) | New value (hex) |
Parity / Stop bits | 40019 (00 12) | float | 0 (00 00 00 00) = n1 | 3 (40 40 00 00) = n2 |
Sensor ID | 40021 (00 14) | float | 1 (3F 80 00 00) = 1 | 149 (43 15 00 00) = 149 |
Baud Rate | 40029 (00 1C) | float | 0 (00 00 00 00) = 2400 | 2 (40 00 00 00) = 9600 |
Ct- Primary cuurent | 40051 (00 32) | float | 5 (40 A0 00 00) = 5 | 50 (42 48 00 00) = 50 or 100 (42 C8 00 00) = 100 |
CyBro-2-230-E configuring SW: eastron_config.zip
PM3-I-D
Power-meters are supplied according to our specifications - no configuration needed before sending.
en/hems/methods_resources/manufacture.txt · Last modified: 2020/07/02 07:09 by amra.begic