                Table of Contents
1-ph current transformer
Split core current transformer 50A
 
| Model number: | CT-1-E-50 | 
|---|---|
| Connect to: | PM1-E-D-CT | 
| terminals 1 -2 | |
| Mounting: | on wire | 
| Dimensions: | 41 × 24 × 27 mm | 
- Split core
- Safe operation
- Mini in size
- Very easy mounting
- Wide inner window
General description
The CT1-E-50 split core current transformer is designed for fast and easy installation. The split core design permits non-contact current measurements through magnetic field induction without requiring that the primary wire be taken off line and disconnected for CT installation. This method permits a safer easy and portable current measurement. An internal precision burden resistor across the secondary winding of the CT provides a safe low voltage output and permits safe opening of the secondary circuit.
Technical specifications
| Frequency | 50-60 Hz | 
| Rated current | 50 A | 
| Accuracy | ±1% from 20% to 120% of rated current | 
| Phase angle | less than 2 degrees at 50% of rated current | 
| Insulation voltage | 600 VAC | 
| Maximum primary voltage | 5000 VAC (insulated conductor) | 
| Dielectric strength | 2.5 kV/1mA/1min | 
| Operating temperature | -15 to 60°C | 
| Operating humidity | < 85 % | 
| Case material | PC/UL94-V0 | 
| Bobin | PBT | 
| Core | Permalloy | 
| Internal structure | Epoxy | 
| Leads | UL 1015, Twisted pair, 22 AWG | 