en:hiq_hw:pm1-e-d-ct
Table of Contents
Single phase power-sensor, CT
1-phase power-sensor, current transformer
Model number: | PM1-E-D-CT |
---|---|
Connect to: | MC-230 |
RS485 power sensor bus A - B | |
Mounting: | DIN rail, 1M, 18 mm |
Dimensions: | 18 × 62 × 119 mm |
Used for measuring power and energy of | |
---|---|
✔ | single-phase energy sources |
✔ | single-phase energy consumers |
Applications
- Digital multi-function power sensor for single phase networks
Features
- DIN rail mounting with 50A current transformer (1-ph current transformer )
- Compact design in a single module 18mm wide
- Seal-able cover(phase and neutral terminals)
General description
The PM1-E-D series is an advanced single phase energy monitoring solution with built-in configuration push button and LCD data display. Particularly indicated for metering active energy and other power parameters. Housing for DIN-rail mounting, IP51 protection degree.
Technical specifications
Technical Data | |
---|---|
Operating Humidity | ≤ 75% |
Storage Humidity | ≤ 95% |
Operating Temperature | -20°C - +50°C |
Storage Temperature | -30°C - +70°C |
International Standard | IEC 62053-21 |
Accuracy | Class 1 |
Mounting | DIN rail (DIN 43880) |
Sealing | IP51 Indoor |
Nominal Voltage Input | (Ph+N) 230V AC (176-276V AC) |
Max Continuous Voltage | 120% of nominal |
AC Voltage Withstand | 4KV for 1 minute |
Impulse Voltage Withstand | 6KV-1.2μS |
Current Input | 0.25-5A(6)A AC RMS |
Operational Current Range | 0.4% Ib-Imax |
Over current withstand | 20Imax for 0.01s |
Nominal Input Current Burden | 0.5VA |
Frequency | 50Hz(±10%) |
Power Consumption | ≤ 2W/10VA/phase |
Accuracy | |
Voltage, Current | 0.5% |
Frequency | 0.2% of Mid-Frequency |
Power Factor | 1% of Unity (0.01) |
Active Power, Apparent Power | ≤ 1% of Range Maximum |
Reactive Power | ≤ 1% of Range Maximum |
Reactive Energy (Varh) | Class 2 |
Active Energy (Wh) | Class 1 |
Current transformer | |
Frequency | 50-60 Hz |
Rated current | 50 A |
Accuracy | from 20% to 120% of rated current |
Phase angle | less than 2 degrees at 50% of rated current |
Insulation voltage | 600 VAC |
Maximum primary voltage | 5000 VAC (insulated conductor) |
Dielectric strength | 2.5 kV/1mA/1min |
Operating temperature | -15 to 60°C |
Operating humidity | < 85 % |
Case material | PC/UL94-V0 |
Bobin | PBT |
Core | Permalloy |
Internal structure | Epoxy |
Leads | UL 1015, Twisted pair, 22 AWG |
Modbus | |
Bus Type | RS485 (Semi-Duplex) |
Protocol | Modbus RTU |
Baud Rate | 1200/2400/4800/9600bps |
Address Range | 1-247 |
Max. Bus Loading | 64pcs |
Communication Distance | 1000 Meters |
Parity | EVEN/ODD/NONE |
Data Bit | 8 |
Stop Bit | 1 |
PM1-E-D-CT Terminals
en/hiq_hw/pm1-e-d-ct.txt · Last modified: 2022/11/24 13:10 by saso_santelj