Three phase power sensor

3-phase power-sensor

Model number: PM3-E-D
Connect to: MC-230
RS485 power sensor bus A - B
Mounting: DIN rail, 1M, 18 mm
Dimensions: 66 × 72 × 100 mm
Used for measuring power and energy of
single/three-phase energy sources
single/three-phase energy consumers

Applications

  • Digital multi-function power sensor for single/three phase networks

Features

  • DIN rail mounting
  • Three Phase 100A Direct Fed
  • Accuracy Class 0.5 (Active Energy)
  • Bi-directlonal Measurement for kW and kWh
  • Configurable Pulsed output (Import/ Export/Nett kWh)
  • Line Frequency
  • Power, maximum power demand and power factor
  • Active energy imported and exported
  • Reactive energy imported and exported
  • Supported Modbus (SDM630Modbus)

General description

SDM630 series measures and displays the characteristics of 1p2w, 3p3w and 3p4w supplies, including voltage, frequency, current, power, active and reactive energy, imported or exported, harmonic etc. Bi-directional measurement makes it an ideal choice for Solar PV measurement. The units support Max. 100A direct connection, saving the cost and avoiding the trouble to connect external CTs. Two pulse outputs and 1 communication port (Mbus/Modbus) are provided for remote monitoring. The unit has been approved to meet the requirements of EU Directive 2014/32/EU.

Technical specifications

Technical Data
Operating Humidity ≤ 75%
Storage Humidity ≤ 95%
Operating Temperature -25°C - +50°C
Storage Temperature -40°C - +70°C
Mounting DIN rail (DIN 43880)
Sealing IP51 Indoor
Auxiliary supply voltage Nominal ± 1%
Auxiliary supply frequency Nominal ± 1%
Frequency 50Hz or 60Hz(±2%)
Power Consumption ≤ 10W
Accuracy
Voltage, Current 0.5%
Frequency 0.2% of Mid-Frequency
Power Factor 1% of Unity (0.01)
Active Power, Apparent Power ± 1% of Range Maximum
Reactive Power ± 1% of Range Maximum
Reactive Energy (Varh) ± 1% of Range Maximum
Active Energy (Wh) Class 1 IEC 62053-21
Current transformer
Frequency 50-60 Hz
Rated current 50 A
Accuracy from 20% to 120% of rated current
Phase angle less than 2 degrees at 50% of rated current
Insulation voltage 600 VAC
Maximum primary voltage 5000 VAC (insulated conductor)
Dielectric strength 2.5 kV/1mA/1min
Operating temperature -15 to 60°C
Operating humidity < 85 %
Case material PC/UL94-V0
Bobin PBT
Core Permalloy
Internal structure Epoxy
Leads UL 1015, Twisted pair, 22 AWG
Modbus
Bus Type RS485 (Semi-Duplex)
Protocol Modbus RTU
Baud Rate 1200/2400/4800/9600bps
Address Range 1-247
Max. Bus Loading 64pcs
Communication Distance 1000 Meters
Parity EVEN/ODD/NONE
Data Bit 8
Stop Bit 1